Perfomance Test Fire Truck & Fire Jeep – PT PERTAMINA Patra Niaga Integrated Terminal Semarang
December 10, 2025
Hydrant Maintenance – PT PLN UBP Jambi Unit PLTMG & CNG Plant Sei Gelam
December 11, 2025

Assessment PMK – PT PERTAMINA PATRA NIAGA – ITC LPG Cilacap

Assessment PMK – PT PERTAMINA PATRA NIAGA – ITC LPG Cilacap

On October 16th, 2025, PT Pro Engineering Utama conduct performance tests at LPG Cilacap 

The performance test of the Aurora L fire pump, rated at 3000 gallons per minute (GPM), was conducted to verify its compliance with operational standards and to ensure its readiness for field deployment. The assessment focused on three primary parameters: engine rotational speed, thermal stability, and hydraulic performance (flow and pressure). All testing procedures were executed under controlled conditions to maintain measurement accuracy and ensure alignment with standard performance evaluation protocols.

Fire Pump Test Result 

During the evaluation, the pump engine operated at a stable 2100 RPM, which represents the designated speed required to achieve maximum hydraulic output. At this RPM, the recorded engine temperature reached 80°C, indicating normal and acceptable thermal performance. This temperature measurement confirms that the cooling and lubrication systems were functioning properly, with no indications of thermal stress or irregular heat buildup throughout the test duration.

Perfomance Test Conclusion Standard Based on NFPA 20

Hydraulic performance results demonstrated that the pump achieved the required operational benchmarks. The measured flow rate reached 3000 GPM, attaining 100% of its rated capacity, which verifies optimal impeller efficiency and unobstructed water passage. The discharge pressure was recorded at 156 psi, corresponding to 97% of the expected rated pressure. While slightly below maximum specification, this value remains within acceptable performance tolerance for operational readiness. Overall, the performance test confirms that the Aurora L fire pump is functioning efficiently and remains suitable for active service.

Share

Related posts

December 11, 2025

Hydrant Maintenance – PT PLN UBP Jambi Unit PLTMG & CNG Plant Sei Gelam


Read more
December 10, 2025

Perfomance Test Fire Truck & Fire Jeep – PT PERTAMINA Patra Niaga Integrated Terminal Semarang


Read more
October 27, 2025

Perfomance Test Diesel Fire Pump & Electric Fire Pump – PT Cikarang Listrindo


Read more

Office
Ruko Palais de Paris Blok F2 No 12
Deltamas Cikarang Pusat Bekasi Jawa Barat
Indonesia 17530
Tel : (021) 89383685
Fax : (021) 29082419
Whatsapp : +62 878 8887 6666

Our Service
Fire Service
Water Work & Irrigation
Residential & Commercial Building Service
Automotive

© 2025 PT. PRO ENGINEERING UTAMA. All Rights Reserved.
    0